Regulations last checked for updates: Oct 15, 2026

Title 40 - Protection of Environment last revised: Oct 13, 2026
Appendix - Table 3 to Subpart Ec of Part 60—Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies
Operating parameters to be monitored Minimum frequency Control system
Data measurement Data recording Dry scrubber followed by fabric filter Wet scrubber Dry scrubber followed by fabric filter and wet scrubber
Maximum operating parameters:
Maximum charge rateContinuous1 × hour✔✔✔
Maximum fabric filter inlet temperatureContinuous1 × minute✔✔
Maximum flue gas temperatureContinuous1 × minute✔✔
Minimum operating parameters:
Minimum secondary chamber temperatureContinuous1 × minute✔✔✔
Minimum dioxin/furan sorbent flow rateHourly1 × hour✔✔
Minimum HCI sorbent flow rateHourly1 × hour✔✔
Minimum mercury (Hg) sorbent flow rateHourly1 × hour✔✔
Minimum pressure drop across the wet scrubber or minimum horsepower or amperage to wet scrubberContinuous1 × minute✔✔
Minimum scrubber liquor flow rateContinuous1 × minute✔✔
Minimum scrubber liquor pHContinuous1 × minute✔✔
authority: 42 U.S.C. 7401
source: 36 FR 24877, Dec. 23, 1971, unless otherwise noted.