Appendix - Table 8 to Subpart VVVVVV of Part 63—Emission Limits and Compliance Requirements for Heat Exchange Systems

Table 8 to Subpart VVVVVV of Part 63—Emission Limits and Compliance Requirements for Heat Exchange Systems

[As required in § 63.11499, you must comply with the requirements for heat exchange systems as shown in the following table.]

For . . . You must . . . Except . . .
1. Each heat exchange system with a cooling water flow rate ≥8,000 gal/min and not meeting one or more of the conditions in § 63.104(a)(1) through (4)a. Except as specified in item 1.c of this table, comply with the monitoring requirements in § 63.104(c), the leak repair requirements in § 63.104(d) and (e), and the recordkeeping and reporting requirements in § 63.104(f); ori. The reference to monthly monitoring for the first 6 months in § 63.104(b)(1) and (c)(1)(iii) does not apply. Monitoring shall be no less frequent than quarterly;
ii. The reference in § 63.104(f)(1) to record retention requirements in § 63.103(c)(1) does not apply. Records must be retained as specified in §§ 63.10(b)(1) and 63.11501(c); and
iii. The reference in § 63.104(f)(2) to “the next semi-annual periodic report required by § 63.152(c)” means the next semiannual compliance report required by § 63.11501(d).
b. Except as specified in item 1.c of this table, comply with the heat exchange system requirements in § 63.104(b) and the requirements referenced thereini. Not applicable.
c. Beginning no later than the compliance dates specified in § 63.11494(i), the exemption conditions specified in § 63.104(a)(3) and (4), and items 1.a and 1.b of this table no longer apply. Instead, comply with the requirements in § 63.104(f) through (j) and (l)i. As specified in § 63.11499(d).
[91 FR 16535, Apr. 1, 2026]
authority: 42 U.S.C. 7401
source: 57 FR 61992, Dec. 29, 1992, unless otherwise noted.