§ 112.25-5 - Failure of power from the normal source.

If there is a reduction of potential of the normal source by 15 to 40 percent, the diesel engine or gas turbine driving the final emergency power source must start automatically with no load on the emergency power source.

authority: 46 U.S.C. 3306,3703; DHS Delegation No. 00170.1, Revision No. 01.2
source: CGD 74-125A, 47 FR 15267, Apr. 8, 1982, unless otherwise noted.
cite as: 46 CFR 112.25-5