§ 111.103-7 - Ventilation stop stations.

Each power ventilation system stop station must:

(a) Be protected by an enclosure with a glass-paneled door on the front;

(b) Be marked, “In Case of Fire Break Glass and Operate Switch to Stop Ventilation;”

(c) Have the “stop” position of the switch clearly identified;

(d) Have a nameplate that identifies the system controlled; and

(e) Be arranged so that damage to the switch or cable automatically stops the equipment controlled.

[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2020-0075, 88 FR 16365, Mar. 16, 2023]
authority: 46 U.S.C. 3306,3703; DHS Delegation No. 00170.1, Revision No. 01.2. Section 111.05-20 and Subpart 111.106 also issued under sec. 617, Pub. L. 111-281, 124 Stat. 2905
source: CGD 74-125A, 47 FR 15236, Apr. 8, 1982, unless otherwise noted.
cite as: 46 CFR 111.103-7