§ 105.13 - Electrical fittings and fixtures.

(a) In compartments or areas containing tanks or pumps handling petroleum products other than Grade E products, no electrical fittings, fixtures, or equipment may be installed or used unless approved for a Class I, Group D hazardous location and labeled as such by UL or another recognized laboratory.

(b) All electrical equipment, fixtures, and fittings located within 10 feet of a vent outlet or a dispensing outlet must be explosion-proof and labeled as such by UL or another recognized laboratory, as suitable for Class I, Group D atmospheres.

(c) All electrical equipment must be grounded to the vessel's common ground.

(d) Tanks, containers, and associated piping systems in use prior to December 1, 1969, on a vessel the construction of which was contracted for before May 31, 1976, are exempt from the requirements of this section provided they are maintained in a condition that the Officer in Charge, Marine Inspection, finds satisfactory, and provided that major repairs or replacement of exempted equipment and systems is in accordance with this part.

authority: 6 U.S.C. 468(b); 33 U.S.C. 1321(j); 46 U.S.C. 2103,3306,3703,4502; 49 U.S.C. 5103; E.O. 12777, sec. 2(d)(2) and (f), 56 FR 54757, 3 CFR, 1991 Comp., p. 351; Department of Homeland Security Delegation No. 0170.1(II) (80), (92.a), (92.b)
source: 81 FR 13283, Mar. 14, 2016, unless otherwise noted.
cite as: 46 CFR 105.13