Regulations last checked for updates: May 19, 2024

Title 30 - Mineral Resources last revised: May 15, 2024
§ 75.521 - Lightning arresters; ungrounded and exposed power conductors and telephone wires.

Each ungrounded, exposed power conductor and each ungrounded, exposed telephone wire that leads underground shall be equipped with suitable lightning arresters of approved type within 100 feet of the point where the circuit enters the mine. Lightning arresters shall be connected to a low resistance grounding medium on the surface which shall be separated from neutral grounds by a distance of not less than 25 feet.

[38 FR 4975, Feb. 23, 1973]
authority: 30 U.S.C. 811,813,957
source: 35 FR 17890, Nov. 20, 1970, unless otherwise noted.
cite as: 30 CFR 75.521