Regulations last checked for updates: Oct 31, 2024
Title 40 - Protection of Environment last revised: Oct 29, 2024
§ 267.190 - Does this subpart apply to me?
This subpart applies to you if you own or operate a facility that treats or stores hazardous waste in above-ground or on-ground tanks under a 40 CFR part 270 subpart J standardized permit, except as provided in § 267.1(b).
(a) You do not have to meet the secondary containment requirements in § 267.195 if your tank systems do not contain free liquids and are situated inside a building with an impermeable floor. You must demonstrate the absence or presence of free liquids in the stored/treated waste, using Method 9095B (Paint Filter Liquids Test) as described in “Test Methods for Evaluating Solid Waste, Physical/Chemical Methods,” EPA Publication SW-846, as incorporated by reference in 40 CFR 260.11.
(b) You do not have to meet the secondary containment requirements of § 267.195(a) if your tank system, including sumps, as defined in 40 CFR 260.10, is part of a secondary containment system to collect or contain releases of hazardous wastes.
§ 267.191 - What are the required design and construction standards for new tank systems or components?
You must ensure that the foundation, structural support, seams, connections, and pressure controls (if applicable) are adequately designed and that the tank system has sufficient structural strength, compatibility with the waste(s) to be stored or treated, and corrosion protection to ensure that it will not collapse, rupture, or fail. You must obtain a written assessment, reviewed and certified by an independent, qualified registered professional engineer, following 40 CFR 270.11(d), attesting that the tank system has sufficient structural integrity and is acceptable for the storing and treating of hazardous waste. This assessment must include, at a minimum, the following information:
(a) Design standard(s) for the construction of tank(s) and/or the ancillary equipment.
(b) Hazardous characteristics of the waste(s) to be handled.
(c) For new tank systems or components in which the external shell of a metal tank or any external metal component of the tank system will be in contact with the soil or with water, a determination by a corrosion expert of:
(1) Factors affecting the potential for corrosion, such as:
(i) Soil moisture content.
(ii) Soil pH.
(iii) Soil sulfides level.
(iv) Soil resistivity.
(v) Structure to soil potential.
(vi) Existence of stray electric current.
(vii) Existing corrosion-protection measures (for example, coating, cathodic protection).
(2) The type and degree of external corrosion protection needed to ensure the integrity of the tank system during the use of the tank system or component, consisting of one or more of the following:
(i) Corrosion-resistant materials of construction such as special alloys, fiberglass reinforced plastic, etc.
(ii) Corrosion-resistant coating (such as epoxy, fiberglass, etc.) with cathodic protection (for example, impressed current or sacrificial anodes) and
(iii) Electrical isolation devices such as insulating joints, flanges, etc.
(d) Design considerations to ensure that:
(1) Tank foundations will maintain the load of a full tank.
(2) Tank systems will be anchored to prevent flotation or dislodgment where the tank system is placed in a saturated zone, or is located within a seismic fault zone subject to the standards of § 267.18(a).
(3) Tank systems will withstand the effects of frost heave.
§ 267.192 - What handling and inspection procedures must I follow during installation of new tank systems?
(a) You must ensure that you follow proper handling procedures to prevent damage to a new tank system during installation. Before placing a new tank system or component in use, an independent, qualified installation inspector or an independent, qualified, registered professional engineer, either of whom is trained and experienced in the proper installation of tank systems or components, must inspect the system for the presence of any of the following items:
(1) Weld breaks.
(2) Punctures.
(3) Scrapes of protective coatings.
(4) Cracks.
(5) Corrosion.
(6) Other structural damage or inadequate construction/installation.
(b) You must remedy all discrepancies before the tank system is placed in use.
§ 267.193 - What testing must I do?
You must test all new tanks and ancillary equipment for tightness before you place them in use. If you find a tank system that is not tight, you must perform all repairs necessary to remedy the leak(s) in the system before you cover, enclose, or place the tank system into use.
§ 267.194 - What installation requirements must I follow?
(a) You must support and protect ancillary equipment against physical damage and excessive stress due to settlement, vibration, expansion, or contraction.
(b) You must provide the type and degree of corrosion protection recommended by an independent corrosion expert, based on the information provided under § 267.191(c), to ensure the integrity of the tank system during use of the tank system. An independent corrosion expert must supervise the installation of a corrosion protection system that is field fabricated to ensure proper installation.
(c) You must obtain, and keep at the facility, written statements by those persons required to certify the design of the tank system and to supervise the installation of the tank system as required in §§ 267.192, 267.193, and paragraphs (a) and (b) of this section. The written statement must attest that the tank system was properly designed and installed and that you made repairs under §§ 267.192 and 267.193. These written statements must also include the certification statement as required in 40 CFR 270.11(d).
§ 267.195 - What are the secondary containment requirements?
To prevent the release of hazardous waste or hazardous constituents to the environment, you must provide secondary containment that meets the requirements of this section for all new and existing tank systems.
(a) Secondary containment systems must be:
(1) Designed, installed, and operated to prevent any migration of wastes or accumulated liquid out of the system to the soil, groundwater, or surface water at any time during the use of the tank system; and
(2) Capable of detecting and collecting releases and accumulated liquids until the collected material is removed.
(b) To meet the requirements of paragraph (a) of this section, secondary containment systems must be, at a minimum:
(1) Constructed of or lined with materials that are compatible with the wastes(s) to be placed in the tank system and must have sufficient strength and thickness to prevent failure owing to pressure gradients (including static head and external hydrological forces), physical contact with the waste to which it is exposed, climatic conditions, and the stress of daily operation (including stresses from nearby vehicular traffic).
(2) Placed on a foundation or base capable of providing support to the secondary containment system, resistance to pressure gradients above and below the system, and capable of preventing failure due to settlement, compression, or uplift.
(3) Provided with a leak-detection system that is designed and operated so that it will detect the failure of either the primary or secondary containment structure or the presence of any release of hazardous waste or accumulated liquid in the secondary containment system within 24 hours.
(4) Sloped or otherwise designed or operated to drain and remove liquids resulting from leaks, spills, or precipitation. You must remove spilled or leaked waste and accumulated precipitation from the secondary containment system within 24 hours, or as promptly as possible, to prevent harm to human health and the environment.
§ 267.196 - What are the required devices for secondary containment and what are their design, operating and installation requirements?
(a) Secondary containment for tanks must include one or more of the following:
(1) A liner (external to the tank).
(2) A double-walled tank.
(3) An equivalent device; you must maintain documentation of equivalency at the facility.
(b) External liner systems must be:
(1) Designed or operated to contain 100 percent of the capacity of the largest tank within its boundary.
(2) Designed or operated to prevent run-on or infiltration of precipitation into the secondary containment system unless the collection system has sufficient excess capacity to contain run-on or infiltration. The additional capacity must be sufficient to contain precipitation from a 25-year, 24-hour rainfall event.
(3) Free of cracks or gaps.
(4) Designed and installed to surround the tank completely and to cover all surrounding earth likely to come into contact with the waste if the waste is released from the tank(s) (that is, capable of preventing lateral as well as vertical migration of the waste).
(c) Double-walled tanks must be:
(1) Designed as an integral structure (that is, an inner tank completely enveloped within an outer shell) so that any release from the inner tank is contained by the outer shell.
(2) Protected, if constructed of metal, from both corrosion of the primary tank interior and of the external surface of the outer shell.
(3) Provided with a built-in continuous leak detection system capable of detecting a release within 24 hours.
§ 267.197 - What are the requirements for ancillary equipment?
You must provide ancillary equipment with secondary containment (for example, trench, jacketing, double-walled piping) that meets the requirements of § 267.195 (a) and (b), except for:
(a) Above ground piping (exclusive of flanges, joints, valves, and other connections) that are visually inspected for leaks on a daily basis;
(b) Welded flanges, welded joints, and welded connections, that are visually inspected for leaks on a daily basis;
(c) Sealless or magnetic coupling pumps and sealless valves, that are visually inspected for leaks on a daily basis; and
(d) Pressurized above ground piping systems with automatic shut-off devices (for example, excess flow check valves, flow metering shutdown devices, loss of pressure actuated shut-off devices) that are visually inspected for leaks on a daily basis.
§ 267.198 - What are the general operating requirements for my tank systems?
(a) You must not place hazardous wastes or treatment reagents in a tank system if they could cause the tank, its ancillary equipment, or the containment system to rupture, leak, corrode, or otherwise fail.
(b) You must use appropriate controls and practices to prevent spills and overflows from tank or containment systems. These include, at a minimum:
(1) Spill prevention controls (for example, check valves, dry disconnect couplings).
(2) Overfill prevention controls (for example, level sensing devices, high level alarms, automatic feed cutoff, or bypass to a standby tank).
(3) Sufficient freeboard in uncovered tanks to prevent overtopping by wave or wind action or by precipitation.
(c) You must comply with the requirements of § 267.200 if a leak or spill occurs in the tank system.
§ 267.199 - What inspection requirements must I meet?
You must comply with the following requirements for scheduling, conducting, and documenting inspections.
(a) Develop and follow a schedule and procedure for inspecting overfill controls.
(b) Inspect at least once each operating day:
(1) Aboveground portions of the tank system to detect corrosion or releases of waste.
(2) Data gathered from monitoring and leak detection equipment (for example, pressure or temperature gauges, monitoring wells) to ensure that the tank system is being operated according to its design.
(3) The construction materials and the area immediately surrounding the externally accessible portion of the tank system, including the secondary containment system (for example, dikes) to detect erosion or signs of releases of hazardous waste (for example, wet spots, dead vegetation).
(c) Inspect cathodic protection systems, if present, according to, at a minimum, the following schedule to ensure that they are functioning properly:
(1) Confirm that the cathodic protection system is operating properly within six months after initial installation and annually thereafter.
(2) Inspect and/or test all sources of impressed current, as appropriate, at least every other month.
(d) Document, in the operating record of the facility, an inspection of those items in paragraphs (a) through (c) of this section.
§ 267.200 - What must I do in case of a leak or a spill?
If there has been a leak or a spill from a tank system or secondary containment system, or if either system is unfit for use, you must remove the system from service immediately, and you must satisfy the following requirements:
(a) Immediately stop the flow of hazardous waste into the tank system or secondary containment system and inspect the system to determine the cause of the release.
(b) Remove the waste from the tank system or secondary containment system.
(1) If the release was from the tank system, you must, within 24 hours after detecting the leak, remove as much of the waste as is necessary to prevent further release of hazardous waste to the environment and to allow inspection and repair of the tank system to be performed.
(2) If the material released was to a secondary containment system, you must remove all released materials within 24 hours or as quickly as possible to prevent harm to human health and the environment.
(c) Immediately conduct a visual inspection of the release and, based upon that inspection:
(1) Prevent further migration of the leak or spill to soils or surface water.
(2) Remove, and properly dispose of, any visible contamination of the soil or surface water.
(d) Report any release to the environment, except as provided in paragraph (d)(1) of this section, to the Regional Administrator within 24 hours of its detection. If you have reported the release pursuant to 40 CFR part 302, that report will satisfy this requirement.
(1) You need not report on a leak or spill of hazardous waste if it is:
(i) Less than or equal to a quantity of one (1) pound; and
(ii) Immediately contained and cleaned up.
(2) Within 30 days of detection of a release to the environment, you must submit a report to the Regional Administrator containing the following information:
(i) The likely route of migration of the release.
(ii) The characteristics of the surrounding soil (soil composition, geology, hydrogeology, climate).
(iii) The results of any monitoring or sampling conducted in connection with the release (if available). If sampling or monitoring data relating to the release are not available within 30 days, you must submit these data to the Regional Administrator as soon as they become available.
(iv) The proximity to downgradient drinking water, surface water, and populated areas.
(v) A description of response actions taken or planned.
(e) Either close the system or make necessary repairs.
(1) Unless you satisfy the requirements of paragraphs (e)(2) and (3) of this section, you must close the tank system according to § 267.201.
(2) If the cause of the release was a spill that has not damaged the integrity of the system, you may return the system to service as soon as you remove the released waste and make any necessary repairs.
(3) If the cause of the release was a leak from the primary tank system into the secondary containment system, you must repair the system before returning the tank system to service.
(f) If you have made extensive repairs to a tank system in accordance with paragraph (e) of this section (for example, installation of an internal liner; repair of a ruptured primary containment or secondary containment vessel), you may not return the tank system to service unless the repair is certified by an independent, qualified, registered, professional engineer in accordance with 40 CFR 270.11(d).
(1) The engineer must certify that the repaired system is capable of handling hazardous wastes without release for the intended life of the system.
(2) You must submit this certification to the Regional Administrator within seven days after returning the tank system to use.
§ 267.201 - What must I do when I stop operating the tank system?
When you close a tank system, you must remove or decontaminate all waste residues, contaminated containment system components (liners, etc.), contaminated soils, and structures and equipment contaminated with waste, and manage them as hazardous waste, unless 40 CFR 261.3(d) applies. The closure plan, closure activities, cost estimates for closure, and financial responsibility for tank systems must meet all of the requirements specified in subparts G and H of this part.
§ 267.202 - What special requirements must I meet for ignitable or reactive wastes?
(a) You may not place ignitable or reactive waste in tank systems, unless:
(1) You treat, render, or mix the waste before or immediately after placement in the tank system so that:
(i) You comply with § 267.17(b); and
(ii) The resulting waste, mixture, or dissolved material no longer meets the definition of ignitable or reactive waste under § 261.21 or § 261.23 of this chapter; or
(2) You store or treat the waste in such a way that it is protected from any material or conditions that may cause the waste to ignite or react; or
(3) You use the tank system solely for emergencies.
(b) If you store or treat ignitable or reactive waste in a tank, you must comply with the requirements for the maintenance of protective distances between the waste management area and any public ways, streets, alleys, or an adjoining property line that can be built upon as required in Tables 2-1 through 2-6 of the National Fire Protection Association's “Flammable and Combustible Liquids Code,” (1977 or 1981), (incorporated by reference, see 40 CFR 260.11).
§ 267.203 - What special requirements must I meet for incompatible wastes?
(a) You may not place incompatible wastes, or incompatible wastes and materials, in the same tank system, unless you comply with § 267.17(b).
(b) You may not place hazardous waste in a tank system that has not been decontaminated and that previously held an incompatible waste or material, unless you comply with § 267.17(b).
§ 267.204 - What air emission standards apply?
You must manage all hazardous waste placed in a tank following the requirements of subparts AA, BB, and CC of 40 CFR part 264. Under a standardized permit, the following control devices are permissible: Thermal vapor incinerator, catalytic vapor incinerator, flame, boiler, process heater, condenser, and carbon absorption unit.
source: 70 FR 53453, Sept. 8, 2005, unless otherwise noted.
cite as: 40 CFR 267.203